wandering1 dafcf8098b test(b6): 台架 @test 闭环复测收口 + 启动行门控修复 + PC 104 主站
B6 台架 @test 闭环复测(B4/B5 验收窗口)完成,DoD 全判据过。

门控修复(首跑 FAIL 实锤的 B5 遗留竞态):
- 现象:protect task start 锚点行字节级交错损坏
  (st[art: cycle=220ms elm=70,两次开机同形复现)
- 根因:启动行在控制台写者注册前打印走无锁裸发,与
  defaultTask 启动日志交错——违反 2026-10-10 门控纪律
  (控制台单写者日志设计说明.md §3.4,adcTask 同款先例)
- 修复:启动锚点行改 dbg_console_writer_ready() 首拍补打

台架与工具:
- .serialtest/config.json:Required 增 protect task start /
  i104 listening on 2404 / [STACK] protect|iec104|heap
- test/host/iec104_master.py:纯标准库 104 主站客户端
  (STARTDT→总召四组+actterm→C_SE 两段写触发 YX15/16 变位
  COT=3→恢复复归→YK11 两段正答→C_RD 读回),往返 18/18
  PASS(d3107f3 与 B7+fix 两版固件)
- 复测 @test PASS:锚点完好 +577ms、9/9 Required、零 [ERR]、
  回读一致;protect free_min 1220(59%)、iec104 2136(83%)、
  新 56KB 堆 min_ever=10000(N-33 抬栈背书就绪)

证据与文档回填:
- boot_log_data 四份快照(含缺陷复现 MISS 件)+ README 登记
- 保护规划 §7 B6 行(B5 台架遗留闭环);控制台单写者 §3.4
  纪律示例 + §11 变更记录;IEC104 §7/§8 主站工具就绪;
  W1 卡 B6 ✅ + N-33 背书 + B7 台架腿注;登记簿 N-33
- 内存台账:+16 B 构建后 ram_baseline/check_mem_numbers 回填

验证:@build 0 错 0 警(Code=205516);ci_local 全绿
(L0 30 钩子 + L0.5 13 套件 826 断言)。
2026-10-12 16:31:33 +08:00

407 lines
16 KiB
Python

#!/usr/bin/env python3
# -*- coding: utf-8 -*-
"""B6 bench leg: IEC 60870-5-104 master client (GI + COV round-trip).
Task card: docs/任务规划/W1-采集保护收尾.md (B6 DoD); protocol baseline:
docs/子系统设计/IEC104上行设计说明.md §3/§4. Constants mirror
App/protocol/iec104/iec104_asdu.h / iec104_link.h.
Flow:
1. TCP connect device :2404, STARTDT act/con (enter RUN).
2. General interrogation C_IC_NA_1 (QOI=20): expect actcon, background
scan (YX double-point group SQ=1 -> YX single-point group SQ=1 ->
YC group SQ=1 -> frequency single point), actterm.
3. Deterministic COV trigger: bench analog inputs are floating (phasor
rms is 0..0.3 raw-code noise only; the standard source belongs to
B10), so we use the two-step C_SE_NC_1 write to temporarily lower
the OC1 current setting (comm addr 0x8858, default 10.0 A) to
0.05 A -> protectTask (20 ms cadence) asserts OC1 -> YX16/YX15
spontaneous (COT=3) uplink. This is exactly the "104 YX linkage"
leg left open by B5. Then restore 10.0 A -> YX16 returns.
4. YK11 (0x600A) two-step select/execute -> positive actcon (reset
request consumed asynchronously by protectTask, B5 contract).
5. C_RD read back 0x8858 ~= 10.0 (restore confirmation).
Exit codes: 0 = all checks PASS; 1 = any check FAIL; 2 = connect or
protocol error. Output is pure ASCII (redirect stdout to archive the
round-trip log as bench evidence).
Usage: python iec104_master.py [--ip 192.168.1.100] [--port 2404]
[--addr 0x8858] [--low 0.05]
[--restore 10.0]
"""
import argparse
import collections
import socket
import struct
import sys
import time
# ---- constants (mirror iec104_asdu.h / iec104_link.h) -----------------------
U_STARTDT_ACT, U_STARTDT_CON = 0x07, 0x0B
U_TESTFR_ACT, U_TESTFR_CON = 0x43, 0x83
T_M_SP_NA_1, T_M_DP_NA_1, T_M_ME_NC_1 = 1, 3, 13
T_C_SE_NC_1, T_C_DC_NA_1 = 50, 52
T_C_IC_NA_1, T_C_RD_NA_1 = 100, 102
COT_BG, COT_SPONT, COT_INIT, COT_REQ = 2, 3, 4, 5
COT_ACT, COT_ACTCON, COT_ACTTERM = 6, 7, 8
COT_PN = 0x40 # COT high byte bit6: negative confirm
RQT_GROUP1 = 20
CA = 1 # common address fixed to 1 in V0.1
SCAN_COTS = (COT_BG, COT_INIT)
YX_NAMES = {15: "YX15 fault-total", 16: "YX16 OC-I", 17: "YX17 OC-II",
18: "YX18 OC-III", 23: "YX23 overload", 31: "YX31 prot-block"}
T0 = time.time()
def log(msg):
print("[%9.3fs] %s" % (time.time() - T0, msg), flush=True)
def hexs(b):
return " ".join("%02X" % x for x in b)
# ---- APCI / ASDU builders ----------------------------------------------------
def u_frame(code):
return bytes([0x68, 0x04, code, 0x00, 0x00, 0x00])
def s_frame(vr):
return bytes([0x68, 0x04, 0x01, 0x00, (vr << 1) & 0xFE, (vr >> 7) & 0x7F])
def i_frame(vs, vr, body):
ctrl = bytes([(vs << 1) & 0xFE, (vs >> 7) & 0x7F,
(vr << 1) & 0xFE, (vr >> 7) & 0x7F])
return bytes([0x68, len(body) + 4]) + ctrl + body
def put_ioa(ioa):
return bytes([ioa & 0xFF, (ioa >> 8) & 0xFF, (ioa >> 16) & 0xFF])
def get_ioa(b, off=0):
return b[off] | (b[off + 1] << 8) | (b[off + 2] << 16)
def asdu(type_id, vsq, cot, cot_hi, ioa=None, payload=b""):
h = bytes([type_id, vsq, cot & 0x3F, cot_hi, CA & 0xFF, (CA >> 8) & 0xFF])
if ioa is not None:
h += put_ioa(ioa)
return h + payload
class Master(object):
"""Minimal 104 master. k/w/t are covered by "S after every recv batch"
(far faster than t1=15s / t2=10s), so no timers are needed here."""
def __init__(self, ip, port):
self.sock = socket.create_connection((ip, port), timeout=10)
self.sock.settimeout(1.0)
self.rx = b""
self.vs = 0
self.vr = 0
self.vr_dirty = False
self.events = collections.deque() # (kind, detail) tuples
self.yx = {} # ioa -> (val, iv)
self.yc = {} # ioa -> (val, qds)
# ---- send ----
def _send(self, data, tag):
log("TX %s %s" % (tag, hexs(data)))
self.sock.sendall(data)
def send_i(self, body, tag):
self._send(i_frame(self.vs, self.vr, body), tag)
self.vs = (self.vs + 1) & 0x7FFF
def _send_s(self):
if self.vr_dirty:
self._send(s_frame(self.vr), "S N(R)=%d" % self.vr)
self.vr_dirty = False
# ---- receive pump ----
def pump_until(self, deadline):
"""Pump RX until deadline (non-blocking semantics for wait_event)."""
while time.time() < deadline:
try:
chunk = self.sock.recv(512)
except socket.timeout:
self._send_s()
continue
if not chunk:
raise RuntimeError("peer closed (EOF)")
self.rx += chunk
while len(self.rx) >= 2 and self.rx[0] == 0x68:
ln = self.rx[1]
if ln < 4 or ln > 253:
raise RuntimeError("bad APDU length %d" % ln)
if len(self.rx) < 2 + ln:
break
apdu, self.rx = self.rx[:2 + ln], self.rx[2 + ln:]
self._handle(apdu)
if self.rx and self.rx[0] != 0x68:
raise RuntimeError("stream desync at 0x%02X" % self.rx[0])
self._send_s()
def wait_event(self, pred, timeout):
deadline = time.time() + timeout
while True:
for i, e in enumerate(self.events):
if pred(e):
return self.events[i]
if time.time() >= deadline:
return None
self.pump_until(min(deadline, time.time() + 1.0))
# ---- frame handling ----
def _handle(self, apdu):
c = apdu[2:6]
b0, b1, b2, b3 = c[0], c[1], c[2], c[3]
if (b0 & 0x01) == 0: # I format
ns = (b0 >> 1) | ((b1 & 0x7F) << 7)
nr = (b2 >> 1) | ((b3 & 0x7F) << 7)
if ns != self.vr:
raise RuntimeError("N(S)=%d out of order (expect %d)"
% (ns, self.vr))
self.vr = (self.vr + 1) & 0x7FFF
self.vr_dirty = True
self._asdu(apdu[6:], nr)
elif (b0 & 0x03) == 0x01: # S format
nr = (b2 >> 1) | ((b3 & 0x7F) << 7)
log("RX S N(R)=%d" % nr)
else: # U format
if b0 == U_STARTDT_CON:
log("RX U STARTDT con")
self.events.append(("startdt_con", None))
elif b0 == U_TESTFR_ACT:
self._send(u_frame(U_TESTFR_CON), "U TESTFR con")
elif b0 == U_TESTFR_CON:
log("RX U TESTFR con")
else:
log("RX U code=0x%02X" % b0)
def _asdu(self, a, nr):
if len(a) < 6:
raise RuntimeError("short ASDU")
type_id, vsq, cot, cot_hi = a[0], a[1], a[2], a[3]
pn = (cot_hi & COT_PN) != 0
sq = (vsq & 0x80) != 0
n = vsq & 0x7F
obj = a[6:]
if type_id in (T_M_SP_NA_1, T_M_DP_NA_1):
pts = []
if sq:
base = get_ioa(obj)
for i in range(n):
pts.append((base + i, obj[3 + i]))
else:
off = 0
for _ in range(n):
pts.append((get_ioa(obj, off), obj[off + 3]))
off += 4
for ioa, raw in pts:
val = (raw & 0x03) if type_id == T_M_DP_NA_1 else (raw & 0x01)
iv = (raw & 0x80) != 0
self.yx[ioa] = (val, iv)
self.events.append(("yx", (ioa, val, iv, cot)))
if ioa in YX_NAMES or cot == COT_SPONT:
log("RX I %s ioa=%d val=%d iv=%d cot=%d [N(R)=%d]"
% ("M_DP" if type_id == T_M_DP_NA_1 else "M_SP",
ioa, val, 1 if iv else 0, cot, nr))
elif type_id == T_M_ME_NC_1:
pts = []
if sq:
base = get_ioa(obj)
for i in range(n):
v = struct.unpack_from("<f", obj, 3 + i * 5)[0]
pts.append((base + i, v, obj[3 + i * 5 + 4]))
else:
off = 0
for _ in range(n):
v = struct.unpack_from("<f", obj, off + 3)[0]
pts.append((get_ioa(obj, off), v, obj[off + 3 + 4]))
off += 8
for ioa, v, qds in pts:
self.yc[ioa] = (v, qds)
self.events.append(("yc", (ioa, v, qds, cot)))
if cot != COT_BG and cot != COT_INIT:
log("RX I M_ME_NC ioa=0x%04X val=%.3f qds=0x%02X cot=%d"
% (ioa, v, qds, cot))
else:
self.events.append(("asdu", (type_id, cot, pn, bytes(obj))))
log("RX I type=%d cot=%d%s body=%s"
% (type_id, cot, " PN" if pn else "", hexs(obj)))
def close(self):
try:
self.sock.settimeout(2.0)
self.sock.close()
except Exception:
pass
# ---- test flow ----------------------------------------------------------------
class Checks(object):
def __init__(self):
self.items = []
def add(self, name, ok, detail=""):
self.items.append((name, bool(ok), detail))
log("CHECK %-28s %s %s" % (name, "PASS" if ok else "FAIL", detail))
def actcon_of(type_id, want_pn=None):
return lambda e: (e[0] == "asdu" and e[1][0] == type_id
and e[1][1] == COT_ACTCON
and (want_pn is None or e[1][2] == want_pn))
def main():
ap = argparse.ArgumentParser(description=__doc__.splitlines()[0])
ap.add_argument("--ip", default="192.168.1.100")
ap.add_argument("--port", type=int, default=2404)
ap.add_argument("--addr", default="0x8858",
help="setpoint comm addr to drive COV (OC1 current)")
ap.add_argument("--low", type=float, default=0.05,
help="temporary low OC1 setting (A) to force pickup")
ap.add_argument("--restore", type=float, default=10.0,
help="OC1 default setting to restore (A)")
args = ap.parse_args()
addr = int(args.addr, 0)
ck = Checks()
log("iec104 master client -> %s:%d (COV trigger: write 0x%X %.2f then "
"restore %.2f)" % (args.ip, args.port, addr, args.low, args.restore))
try:
m = Master(args.ip, args.port)
except Exception as e:
log("CONNECT FAIL: %r" % (e,))
return 2
rc = 2
try:
# 1. STARTDT
m._send(u_frame(U_STARTDT_ACT), "U STARTDT act")
ck.add("startdt_con", m.wait_event(
lambda e: e[0] == "startdt_con", 5.0) is not None)
# 2. first general interrogation
m.send_i(asdu(T_C_IC_NA_1, 1, COT_ACT, 0, ioa=0,
payload=bytes([RQT_GROUP1])),
"I C_IC act (QOI=20)")
ck.add("gi_actcon", m.wait_event(actcon_of(T_C_IC_NA_1, False),
5.0) is not None)
def scan_yx(ioa):
return lambda e: (e[0] == "yx" and e[1][0] == ioa
and e[1][3] in SCAN_COTS)
ck.add("scan_yx_dp(ioa4)", m.wait_event(scan_yx(4), 10.0) is not None)
ck.add("scan_yx_sp(ioa16)", m.wait_event(scan_yx(16), 10.0) is not None)
ck.add("scan_yc(ioa0x4018)", m.wait_event(
lambda e: (e[0] == "yc" and e[1][0] == 0x4018
and e[1][3] in SCAN_COTS), 10.0) is not None)
ck.add("scan_freq(ioa0x401D)", m.wait_event(
lambda e: (e[0] == "yc" and e[1][0] == 0x401D
and e[1][3] in SCAN_COTS), 10.0) is not None)
ck.add("gi_actterm", m.wait_event(
lambda e: (e[0] == "asdu" and e[1][0] == T_C_IC_NA_1
and e[1][1] == COT_ACTTERM), 10.0) is not None)
v16 = m.yx.get(16)
ck.add("baseline_yx16_off", v16 is not None and v16 == (0, False),
"yx16=%r" % (v16,))
# 3. COV up: lower OC1 setting (two-step C_SE_NC_1)
def se(select):
pl = struct.pack("<f", args.low) + bytes([0x80 if select else 0x00])
return asdu(T_C_SE_NC_1, 1, COT_ACT, 0, ioa=addr, payload=pl)
m.send_i(se(True), "I C_SE select 0x%X = %.3f" % (addr, args.low))
ck.add("se_select_con", m.wait_event(actcon_of(T_C_SE_NC_1, False),
5.0) is not None)
m.send_i(se(False), "I C_SE execute 0x%X = %.3f" % (addr, args.low))
ck.add("se_execute_con", m.wait_event(actcon_of(T_C_SE_NC_1, False),
5.0) is not None)
m.events.clear() # drop any echo/ack noise before COV watch
def spont(ioa, val):
return lambda e: (e[0] == "yx" and e[1][0] == ioa
and e[1][1] == val and e[1][3] == COT_SPONT)
ck.add("spont_yx16_ON", m.wait_event(spont(16, 1), 8.0) is not None)
ck.add("spont_yx15_ON", m.wait_event(spont(15, 1), 3.0) is not None)
# 4. COV down: restore OC1 default setting
def se_restore(select):
pl = struct.pack("<f", args.restore) + bytes([0x80 if select else 0x00])
return asdu(T_C_SE_NC_1, 1, COT_ACT, 0, ioa=addr, payload=pl)
m.send_i(se_restore(True), "I C_SE select 0x%X = %.3f (restore)"
% (addr, args.restore))
ck.add("se_restore_select_con",
m.wait_event(actcon_of(T_C_SE_NC_1, False), 5.0) is not None)
m.send_i(se_restore(False), "I C_SE execute 0x%X = %.3f (restore)"
% (addr, args.restore))
ck.add("se_restore_execute_con",
m.wait_event(actcon_of(T_C_SE_NC_1, False), 5.0) is not None)
m.events.clear()
got_spont_off = m.wait_event(spont(16, 0), 5.0) is not None
if got_spont_off:
ck.add("yx16_OFF", True, "via spontaneous COT=3")
else:
# floating-input chatter may have returned YX16 before the
# restore write; fall back to a second GI background scan.
log("no spont OFF within 5s -> second GI background scan")
m.send_i(asdu(T_C_IC_NA_1, 1, COT_ACT, 0, ioa=0,
payload=bytes([RQT_GROUP1])),
"I C_IC act #2 (QOI=20)")
ok_term = m.wait_event(
lambda e: (e[0] == "asdu" and e[1][0] == T_C_IC_NA_1
and e[1][1] == COT_ACTTERM), 15.0) is not None
ck.add("yx16_OFF", ok_term and m.yx.get(16) == (0, False),
"via 2nd GI scan, yx16=%r" % (m.yx.get(16),))
# 5. YK11 two-step (positive confirm; reset consumed by protectTask)
m.send_i(asdu(T_C_DC_NA_1, 1, COT_ACT, 0, ioa=0x600A,
payload=bytes([0x82])), "I C_DC YK11 select (QDC=82H)")
ck.add("yk11_select_con", m.wait_event(actcon_of(T_C_DC_NA_1, False),
5.0) is not None)
m.send_i(asdu(T_C_DC_NA_1, 1, COT_ACT, 0, ioa=0x600A,
payload=bytes([0x02])), "I C_DC YK11 execute (QDC=02H)")
ck.add("yk11_execute_con", m.wait_event(actcon_of(T_C_DC_NA_1, False),
5.0) is not None)
# 6. C_RD read back the restored setpoint
m.send_i(asdu(T_C_RD_NA_1, 1, COT_REQ, 0, ioa=addr),
"I C_RD 0x%X" % addr)
e = m.wait_event(lambda e: (e[0] == "yc" and e[1][0] == addr
and e[1][3] == COT_REQ), 5.0)
ck.add("rd_setpoint_10.0",
e is not None and abs(e[1][1] - args.restore) < 0.1,
"read=%.3f" % (e[1][1],) if e else "no response")
m.close()
rc = 0 if all(ok for _, ok, _ in ck.items) else 1
except Exception as e:
log("PROTOCOL ERROR: %r" % (e,))
rc = 2
n_ok = sum(1 for _, ok, _ in ck.items)
log("SUMMARY: %d/%d checks PASS -> %s"
% (n_ok, len(ck.items), "PASS" if rc == 0 else ("FAIL" if rc == 1 else "ERROR")))
return rc
if __name__ == "__main__":
sys.exit(main())